Single-phase Chint energy meter is designed to monitor power and to measure the energy in power systems. It belongs to a generation of programmable intelligent instruments, integrated with monitoring and communication functions. It is mainly thought to be used for real-time measurement and display for electrical parameters such as voltage, current, active power, reactive power, frequency, power factor...
Compatible with SAj inverters
DUE TO LIMITED STOCK, THIS EQUIPMENT IS ONLY SOLD TOGETHER WITH ONE OF THE COMPATIBLE INVERTERS.
* Technical support not included. Eligible separately here.
Secure payment
Shipping policy
Return policy
| Technical parameters |
Index |
||||
|
Input signal |
Voltage |
Wiring mode |
Single phase |
||
|
Voltage specification |
AC 220V |
||||
|
Specified working voltage range |
0.9Un~1.1Un; the extensional work voltage range: 0.8Un~1.2Un |
||||
|
Consumption of the voltage circuit |
≤5VA/1W |
||||
|
Resistance |
>500kΩ |
||||
|
Current |
Rated value |
Input via CT/PT: AC1.5(6)A |
|||
|
Overload Current |
Input via CT/PT: instant:201max, time of application is 0.5s |
||||
|
Consumption of the current circuit |
≤2VA |
||||
|
Resistance |
<20mΩ |
||||
|
Frequency |
Input range |
(50/60±5%)Hz |
|||
|
Clock |
Clock battery capacity |
≥1200mAh |
|||
|
Clock accuracy class(daily error) |
<0.5s/d(23℃) |
||||
|
Output |
Display |
Segment LCD |
|||
|
Measurement parameters and grade |
Voltage Class 0.5; Current Class 0.5; Power factor Class 1; |
||||
|
Energy |
Multi-rate energy |
Support multi-rate measurement of passive, negative total active power |
|||
|
Max. demand record |
Support Max. demand record of passive, negative total active power, demand interval and slip time can be set |
||||
|
Pulse constant |
AC200V |
AC1.5(6)A |
6400imp/kWh |
||
|
AC220V |
AC5(60)A/AC5(80)A |
800imp/kWh |
|||
|
Pulse signal output |
Provide 1 set(active energy) optical signal and optocoupler isolated open collector electrical signal pulse output, pulse length:80ms±16ms |
||||
|
Communication |
RS485 communication |
Support or DL/T645-2007 communication protocol, customizable MODBUS-RTU communication protocol, the communication baud rate 1200bps, 2400bps,4800bps,9600bps can be set, assumed to be 2400bps |
|||
|
IR communication |
Support DL/T645-2007 communication protocol, customizable for MODBUS-RTU communication protocol, Infrared wave length:900nm~1000nm Communication baud rate: 1200bp Communication angle: ≥±15° Communication distance: ≥4m |
||||