El vatímetro Chint Monofásico DDSU666 está diseñado para monitorización de potencia y medición de energía en sistemas de potencia. Pertenece a una generación de instrumentación inteligente y programable, integrada con funciones de medida y comunicación, principalmente para ser usada en mediciones en tiempo real y visualización de parámetros eléctricos como voltaje, corriente, potencia activa, potencia reactiva, frecuencia, factor de potencia, etc.
Compatibilidad con los inversores SAJ
* Soporte técnico no incluido.
Pago seguro
Política de envío
Política de devolución
| Technical parameters |
Index |
||||
|
Input signal |
Voltage |
Wiring mode |
Single phase |
||
|
Voltage specification |
AC 220V |
||||
|
Specified working voltage range |
0.9Un~1.1Un; the extensional work voltage range: 0.8Un~1.2Un |
||||
|
Consumption of the voltage circuit |
≤5VA/1W |
||||
|
Resistance |
>500kΩ |
||||
|
Current |
Rated value |
Input via CT/PT: AC1.5(6)A |
|||
|
Overload Current |
Input via CT/PT: instant:201max, time of application is 0.5s |
||||
|
Consumption of the current circuit |
≤2VA |
||||
|
Resistance |
<20mΩ |
||||
|
Frequency |
Input range |
(50/60±5%)Hz |
|||
|
Clock |
Clock battery capacity |
≥1200mAh |
|||
|
Clock accuracy class(daily error) |
<0.5s/d(23℃) |
||||
|
Output |
Display |
Segment LCD |
|||
|
Measurement parameters and grade |
Voltage Class 0.5; Current Class 0.5; Power factor Class 1; |
||||
|
Energy |
Multi-rate energy |
Support multi-rate measurement of passive, negative total active power |
|||
|
Max. demand record |
Support Max. demand record of passive, negative total active power, demand interval and slip time can be set |
||||
|
Pulse constant |
AC200V |
AC1.5(6)A |
6400imp/kWh |
||
|
AC220V |
AC5(60)A/AC5(80)A |
800imp/kWh |
|||
|
Pulse signal output |
Provide 1 set(active energy) optical signal and optocoupler isolated open collector electrical signal pulse output, pulse length:80ms±16ms |
||||
|
Communication |
RS485 communication |
Support or DL/T645-2007 communication protocol, customizable MODBUS-RTU communication protocol, the communication baud rate 1200bps, 2400bps,4800bps,9600bps can be set, assumed to be 2400bps |
|||
|
IR communication |